3522路线检测

当前位置:3522路线检测 > 资讯资讯 > 行业资讯 

常见空调报警原因


 ?      1、压缩机高压报警GOb3522vip.com

①高压开关故障或控制干扰导致误报警;GOb3522vip.com

②风冷冷凝器灰尘较多,冷却能力下降;GOb3522vip.com

③风冷冷凝器风机电源断开;GOb3522vip.com

④风冷冷凝器调速器断路;GOb3522vip.com

⑤风冷冷凝器温度开关异常;GOb3522vip.com

⑥水冷设备冷凝器水流量丢失或冷却水温异常;GOb3522vip.com

⑦排气管路异常油堵或异物堵塞;GOb3522vip.com

⑧制冷剂充注过量。GOb3522vip.com

2、压缩机低压告警GOb3522vip.com

①低压开关故障或控制干扰导致误告警;GOb3522vip.com

②室内过滤网堵塞造成风量不足;GOb3522vip.com

③室内主风机故障。风量下降;GOb3522vip.com

④温度设定点错误,回风温度过低;GOb3522vip.com

⑤冷启动延时设置不够,冬季启动困难;GOb3522vip.com

⑥制冷剂充注量不足或制冷剂泄漏。GOb3522vip.com

3、低湿告警GOb3522vip.com

①低湿告警设定点错误;GOb3522vip.com

②机房密封不良,房门开启频繁;GOb3522vip.com

③加湿器供水堵塞、水压过低、停水;GOb3522vip.com

④加湿罐结垢较多;GOb3522vip.com

⑤加湿电极结垢较多。GOb3522vip.com

4、高温告警GOb3522vip.com

①高温告警设定点错误;GOb3522vip.com

②犯贱热负荷较大或房门开启频繁;GOb3522vip.com

③其他异常告警导致压缩机停机;GOb3522vip.com

④冷冻水设备冷冻水流量丢失或冷冻水温异常。GOb3522vip.com

5、地板漏水告警GOb3522vip.com

①漏水检测探针接触到导体;GOb3522vip.com

②排水管堵塞,有水从加湿水盘溢出;GOb3522vip.com

③排水管破裂或泄漏;GOb3522vip.com

④设备中异常部位的凝结水滴落;GOb3522vip.com

⑤其他异常途径的水淌入地下。GOb3522vip.com

6、气流丢失GOb3522vip.com

①气流不足检测热敏电阻与发热电阻距离过近;GOb3522vip.com

②气流压差传感器的取样气管堵塞或位置偏移;GOb3522vip.com

③传感器板与显示控制板连接松脱;GOb3522vip.com

④供电反相;GOb3522vip.com

⑤室内送分部分故障;GOb3522vip.com

⑥过滤网堵塞。GOb3522vip.com